Conductor screen: Conductor screen layer of extruded semi-conducting compound forming anon-metallic screen. The extruded semi-conducting compound shall be firmly bonded to the insulation.
Insulation conductor screen: Extruded XLPE cured with dry curing process.
Insulation screen: a- non metallic screen applied directly over the XLPE insulation and shall consist of a combination of an extruded semi-conducting compound layer and of 50% overlap semi-conducting swelling tape.
b- Metallic screen made of combination of copper wires and copper tape over the insulation. The equivalent cross section area equals 35 mm˛.
Water proof tape: A layer of swelling tape for water proofing
PVC Jacket: Over all extruded PVC seamless sheath to prevent moisture from penetration and provides good corrosion protection, thickness not less than 3 mm and to be anti-termite treated. Marking of name, year of manufacture, voltage and cross-section stamped each one meter
Packing: The required cable lengths are to be supplied on steel or wooden drums of length 500 m cable drum plus or minus 5 %.
Training: The offer should include training (4 person) for ten days in manufacturer company site.