Skin Point Thermocouples
Reference: 11/2012/E 5/17/2012, Location: Middle East
Category: Thermocouples
Scope of Work
Item 001 QTY=20, Skin Point Thermocouples for Furnace 501-B Description: Type TC 720 sheathed thermocouple with conductor wire. Type and number of sensors: 1 x Type "K" (NiCr-Ni). Sensor limiting error: Class 2 per DIN EN 60584. Measuring point: insulated. Process connection: Weld on sheet 25 x 25 x 3.2 mm (wxlxh). Sheath material: Ni Alloy 2.4816 (Inconel 600) Sheath diameter: 8.0 mm. Nominal Length: 1500 mm Conductor: Thermo wire, Diameter 0.5 mm, lead length 100 mm. Service: Tube Skin of furnace Temperature: 500-1000 ºC
|