Gulf Oil and Gas
      Go to 3D Projects Premium Content Zone >>  |  Logon Oil and Gas

Procurement of Electrical Cables
Reference: SSI9948P19 12/3/2018, Location: Asia
Category: Cables

Scope of Work
The company announces its need for Procurement of Electrical Cables (QTY- 6000 M).

The instruments to be supplied are as follows: -
- Item 001 Qty=3000 of Cables, Conductors, Wires & Accessories Cable, 3.5C x 120 mm2, 1100V, PVCA Alu.
Size: 3.5Cx120 mm2.
Voltage Grade: 1100V.
Colour: Black.
Conductor Material: Stranded compact circular/shaped Aluminium.
Shape: Complete round on outer side.
Insulation: PVC.
Filler & Inner Sheath: Unvulcanized rubber/ Thermoplastic materials/ Proofed tape (for inner sheath only).
Outer Sheath: PVC.
Armour: Galvanised Steel Tape/Wire.
Min Length: 500Mtr.
Applicable Standard: IS-1554 (part-1)-1988 (with latest amendments if any)
Marking:
a) Manufacture's name, voltage grade, length (in metres), size of cable, year of manufacture and the letters 'ELECTRIC' shall be printed, indented or embossed on the sheath of the cable throughout the length. The distance between any two consecutive printings, indentations or embossings shall be not more than 1 m.
b) Cable drum shall be marked with manufacture's name, voltage grade, size of cable, cable code, year of manufacturing, length of cable, Number of lengths on the drum (if more than one); gross weight, ISI mark & OIL's purchase order number with suitable paint in permanent manner.
Make: Any brand with valid BIS manufacturing license & type test certificates

- Item 002 Qty=3000 of Cable, 1C x 16 mm2, 1100V, PVC Alu. (Earthing).
Size: 1Cx16 mm2.
Voltage Grade: 1100V.
Colour: Black.
Conductor Material: Stranded compact circular Aluminium.
Shape: Complete round on outer side.
Insulation: PVC.
Sheath: PVC.
Min Length: 100Mtr.
Applicable Standard: IS-1554 (part-1)-1988 (with latest amendments if any).
Marking:
a) Manufacture's name, voltage grade, length (in metres), size of cable, year of manufacture and the letters 'Earthing' and 'ELECTRIC' shall be printed, indented or embossed on the sheath of the cable throughout the length. The distance between any two consecutive printings, indentations or embossings shall be not more than 1 m.
b) Cable drum shall be marked with manufacture's name, voltage grade, size of cable, cable code, year of manufacturing, length of cable, Number of lengths on the drum (if more than one); gross weight, ISI mark & OIL's purchase order number with suitable paint in permanent manner.
Make: Any brand with valid BIS manufacturing license & type test certificates



Related Prooducts: Cables Accumulators and Storage batteries  Ammeters, Voltmeters, ect.  Batteries  Cable Trays  Cables  Cathodic Protection  Circuit Breakers  Contactors  Control Panels  Earthing materials  Electric fittings & junction box  Frequency Inverter  General  Lighting  Panel Components  Starter  Steel Panels  Switches  Transformers  Umbilical Lines  UPS 

Related Tenders: Accumulators and Storage batteries  Batteries  Cable Trays  Cables  Cathodic Protection  Circuit Breakers  Contactors  Control Panels  Earthing materials  Electric fittings & junction box  Frequency Inverter  General  Lighting  Panel Components  Starter  Switches  Transformers  Umbilical Lines  UPS 

Hyundai Orders World’s First ME-GA
World-First Order for Methanol Engine within Container Segment
MAN Energy Solutions Confirms World-First LAES Project
MAN Energy & ANDRITZ Hydro Agree on Hydrogen Cooperation
Exploration
Development
Oil & Gas Companies

Gulf Oil and Gas E-Marketplace - Premium Content

Copyright © Universal Solutions S.A.E. All rights reserved. Privacy Policy. - Contact Us